XLPE/SHF1 – 500 e 1000V – 90ºC
NBR 16442
IEC 60502-1

Unarmoured cables: 6 x Outer diameter
Armored cables: 12 x Outer diameter
40N/mm² applied on copper conductors.
| Conductor | Bare copper wires, soft temper. Stringing: Class 5, according to NBR NM 280. Flexible. |
|---|---|
| Isolation | XLPE – Cross-linked polyethylene, black numbered sequentially. |
| Cover | SHF1 - halogen-free thermoplastic compound, in black, with rip cord, cylindrical finish. |
Upon request, instrumentation cables can be manufactured with the following construction options:
| Conductor | Tinned copper; Class 5 copper. |
|---|---|
| Identification | Colored veins; Green/yellow vein (protective conductor) |
| Isolation | HEPR (90ºC) Polyethylene PE (70°C). |
| Shielding | Copper braid + copper tape (E+B); |
| Frame | Helical Steel Wire (SWA). |
| Cover | PE (Polyethylene ST3); SHF2 – halogen-free thermosetting compound. |
| Color | Other colors on request |
| NBR NM 280 | Insulated cable conductors (IEC 60228 MOD). |
|---|---|
| NBR 6251 | Power cables with extruded insulation for voltages from 1kV to 30kV. |
| NBR 10300 | Non-halogenated control cables with low smoke emission for voltages up to 1kV. |
| IEC 60502-1 | Power cables with extruded insulation for voltages from 1kV to 30kV. |
| Voltage Test | 1.5 kV / 5 minutes: 500V (sections 0.5 to 1.0 mm2) 3.5 kV / 5 minutes: 1000V (sections 1.5 to 10 mm2) |
|---|---|
| Resistence test of isolation | 300 to 500V / 1 to 5 minutes |
| Section (mm2) | Max. DCR @20ºC (ohm/km) |
|---|---|
| 0,5 | 39 |
| 0,75 | 26 |
| 1,0 | 19,5 |
| 1,5 | 13,3 |
| 2,5 | 7,98 |
| 4,0 | 4,95 |
| 6,0 | 3,30 |
| 10 | 1,91 |
Maximum traction: 40 N/mm² applied on copper conductors.
Copyright © 2021 – Poliron. All rights reserved | By: Movimento br
Fill out the form below to learn more about the only cables in Brazil with a 5-year warranty and the best delivery time on the market!